
volume capacity of the system. It also uses a reserve value to
determine if a regeneration is necessary. If the water usage since
the last regeneration is greater than the system capacity minus the
reserve, a regeneration is needed.
Note: If the water usage exceeds 150% of the system capacity
between regenerations, the control will automatically call for a
second regeneration the next day even if no water is used. This
feature is included to make sure that an exhausted resin bed is
completely recharged.
Reserve Options
There are two types of reserve options for this control: xed reserve
and historical water usage pattern. They are selected with Parameter
P15.
Fixed Reserve
When the xed reserve is selected, the control multiplies the
maximum system capacity by the percent value set in Parameter
P16 and uses the result as a reserve.
Water Usage Pattern
The other reserve option allows the control to adjust the reserve
based upon the historical water usage pattern of the system. The
control keeps track of the water usage for each day of the week
and uses that day’s average usage multiplied by 1.2 as the reserve
for that day. Every day at the Time of Regeneration, the control
recalculates the day’s average water usage. If less than 10% of a
day’s average water usage is used, the control will not change the
day’s average. If more than twice the day’s average is used, the
control uses the actual usage in the reserve calculation.
Since a new installation has no history of water usage, the control
multiplies the percent of capacity value set in Parameter P16 by the
total system capacity to determine starting average for each day of
the week. The factory set default value for P16 is 30 which means
that 30% of the total system capacity is used for the starting average
for each day.
Program Parameter P15 is also used to select whether the control
waits until the Time of Regeneration set in Parameter P2 to start
a regeneration, or if the control should begin a regeneration
immediately when the capacity remaining is less than the reserve.
Removing the Valve Assembly for Servicing
1. Unplug the power cord.
2. Shut off water supply or put bypass valve(s) into bypass
position.
3. Remove cover and with screwdriver, relieve tank pressure by
pushing open valve No. 7 (rear apper) on control as shown
(Figure 8).
Figure 8
4. When used with a globe valve bypass, loosen and detach
the inlet, outlet, brine and drain lines from the valve. If
using the 1265 bypass, loosen and remove valve from
bypass as well as loosening and removing the brine and
drain lines.
5. Unscrew (counterclockwise) and remove valve from tank.
6. To replace the control valve, reverse the above procedure
.
Komentáře k této Příručce